Product Description
Large Ground Grid Tester 

Darui Electric recommends:




Large Ground Grid TesterProduct Functions

1. Accurately measure the grounding impedance, grounding resistance, and grounding reactance of large grounding grids;

2. Accurately measure the surface potential gradient of the large grounding grid area;


3. Accurately measure the contact potential difference, contact voltage, step potential difference, and step voltage of the large grounding grid;


4. Measure soil resistivity


5. Accurately measure the transfer potential of the large grounding grid;


6. Measure the continuity resistance of the grounding down conductor;

System Parameters

Power supply voltage: AC220V or 380V, 50Hz

Output power: 10KW (2KW~20KW optional, customizable)


Output voltage: 0~600V or 1000V (customizable)


Test output current: 0~50A


Frequency adjustment range: 45~65Hz


Step frequency: 1Hz


Anti-interference capability: passband ±0.3Hz, attenuation >80dB/Hz


Measurement range: 0.001~1000Ω


Resolution: 1mΩ


Measurement accuracy: 1.0 class



2. The length ratio of the current test wire to the voltage test wire is 1:0.618, and the length of the current test wire should be 3 to 5 times the diagonal of the ground grid.


3. Connect one end of the current test wire and the voltage test wire to the instrument according to the specified length, and lay them out in parallel. Connect the other ends to the two ground stakes respectively (as shown in Figure 2).


4. Check the laid test wires. Connect one end of the multimeter to the current wire or voltage wire, and the other end to the ground grid wire. If there is no resistance reading, it indicates an open circuit. Confirm it is intact before testing.


5. After confirming the connections are correct, connect the instrument to an AC220V/50HZ power supply and power it on.


6. Press the measurement key to start the measurement.


7. After the instrument indicates the test is complete, record the test data.


8. Turn off the instrument power, remove the connections, and the test process is complete.




Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.
WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us