5A Ground Grid Earth Resistance Tester
Darui Electric recommends:
Product Overview:
5A Ground Grid Earth Resistance Tester is a software and hardware system mainly used for accurately measuring grounding characteristic parameters of large grounding grids, such as grounding impedance, grounding resistance, grounding reactance, field surface potential gradient, contact potential difference, contact voltage, step potential difference, step voltage, transfer potential, grounding down-conductor continuity resistance, and soil resistivity. It adopts point-by-point frequency conversion with strong anti-interference capability, enabling accurate measurement of data at power frequency 50Hz even in strong interference environments. The system has high output power (2-20KW), high voltage (0-1000V), and large output current (0-50A), which will not cause excessive potential rise of the grounding device during testing. Additionally, it possesses strong anti-interference ability, allowing measurement without power outage.
Product Aliases:
Large Ground Grid Grounding Impedance Tester, 5A Ground Grid Earth Resistance Tester, Large Ground Grid Grounding Impedance Test System, Variable Frequency High Current Multifunctional Ground Grid Grounding Characteristic Measurement System, Grounding Impedance Test, Grounding Impedance Tester, Large Ground Grid Variable Frequency Grounding Impedance Characteristic Test System, Grounding Device Characteristic Parameter Measurement System, Variable Frequency High Current Multifunctional Tester, Offset Frequency Grounding Impedance Tester, Anti-interference Offset Frequency Ground Grid Grounding Impedance Tester, Offset Frequency Grounding Resistance Tester
Product Functions:
1. Accurately measure grounding impedance, grounding resistance, and grounding reactance of large grounding grids;
2. Accurately measure the field surface potential gradient of large grounding grids;
3. Accurately measure contact potential difference, contact voltage, step potential difference, and step voltage of large grounding grids;
4. Measure soil resistivity;
5. Accurately measure transfer potential of large grounding grids;
6. Measure the continuity resistance of grounding down-conductors;
Technical Specifications:
1. Impedance measurement range: 0Ω to 200Ω
2. Resolution: 0.001Ω
3. Measurement error: ±(reading × 2% + 0.005Ω)
4. Anti-interference capability against 50Hz power frequency voltage: 10V
5. Test current waveform: sine wave
6. Test current frequency: automatic 45Hz/55Hz dual frequency, with multiple frequency conversion options for selection
7. Maximum output current: 5A
8. Maximum output voltage: 400V
9. Measurement line requirements: current line copper core cross-sectional area ≥ 2.0mm2
Voltage line copper core cross-sectional area ≥ 1.5mm2
10. Power supply: AC220V±10%, 50Hz

Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.