全自动Dielectric Loss Tester-扬州达瑞

HKC-GP9570 Transformer Oil Photoacoustic Spectroscopy Online Monitoring System - Yangzhou Darui

Published: 2020-08-25 14:01:00

Views: 2922

Category: Oil Chromatography Online Monitoring

Product Description


HKC-GP9570 Transformer Oil Photoacoustic Spectroscopy Online Monitoring System 


Darui Electric recommends:


I. Overview of HKC-GP9570 Transformer Oil Photoacoustic Spectroscopy Online Monitoring System



    The HKC-GP9570 transformer oil photoacoustic spectroscopy online monitoring system is used for online analysis and fault diagnosis of dissolved gases in power transformer oil, suitable for power transformers, arc furnace transformers, reactors, and instrument transformers at 110kV and above voltage levels, as well as other oil-immersed high-voltage equipment. The HKC-GP9570 system can quantitatively, automatically, and rapidly monitor online the content and growth rate of dissolved fault gases in the oil of transformers and other oil-immersed power high-voltage equipment, and through the fault diagnosis expert system, it can early predict equipment fault hidden dangers, avoid equipment accidents, reduce significant losses, and improve the reliability of equipment operation. As an authoritative product in the field of oil photoacoustic spectroscopy online monitoring, this system provides a stable and reliable solution for online remote DGA analysis of power transformers, and is a strong guarantee for the implementation of the condition-based maintenance system in the power system.



 



 



II. Composition of HKC-GP9570 Transformer Oil Photoacoustic Spectroscopy Online Monitoring System



    The HKC-GP9570 transformer oil photoacoustic spectroscopy online monitoring system consists of a field monitoring unit (photoacoustic spectroscopy data collector), a master station unit (data processing server), and monitoring software. The field monitoring unit, i.e., the photoacoustic spectroscopy data collector, is composed of an oil sample collection unit, an oil-gas separation unit, a gas detection unit, a data acquisition unit, a field control processing unit, a communication control unit, and auxiliary units. The auxiliary units include transformer interface flanges, oil pipes, and communication cables. 



 



III. Working Principle of HKC-GP9570 Transformer Oil Photoacoustic Spectroscopy Online Monitoring System



    When the HKC-GP9570 transformer oil photoacoustic spectroscopy online monitoring system is working, it uses a vacuum differential pressure method to draw transformer oil into the oil sample collection unit, and circulates the oil sample through an oil pump; the oil-gas separation unit quickly separates dissolved gases in the oil into the gas chamber, and the built-in micro gas sampling pump transports the separated gas sample to the photoacoustic spectroscopy gas chamber; the data acquisition unit completes AD data conversion and acquisition, and the embedded processing unit stores, calculates, and analyzes the collected data, and uploads the data to the data processing server (installed in the main control room) via RS485 to Ethernet, and finally the HKC-GP9570 condition monitoring software performs data processing and fault analysis.



 



IV. Main Technical Parameters of HKC-GP9570 Transformer Oil Photoacoustic Spectroscopy Online Monitoring System



 



1. Working environment temperature: -40℃~+55℃



2. Working environment humidity: relative humidity 5~95% (no condensation inside the device, and no icing)



3. Atmospheric pressure: 70kPa~110kPa; 50kPa~110kPa



4. Working power supply: AC220V±10%, 50Hz



5. Monitoring components: H2, CO, CO2, CH4, C2H2, C2H4, C2H6, H2O, O2, N2 and other gas components and total hydrocarbon content;



6. Minimum monitoring cycle: 20 minutes, and above 20 minutes can be set by the user



7. Sampling method: Circulating sampling, safely and truly reflecting the actual gas conditions in the transformer



8. Oil-gas separation method: Negative pressure dynamic headspace purge and degassing method



9. Data storage life: ≥10 years



10.  Monitoring gas     Measurement range (ppm)      Minimum detection limit



     1) H2          1~5000.0         1ppm NA



     2) CO         1~50,000.0           11



     3) CO2        2~50,000.0            2



     4) CH4       0.1~50,000.0          0.1


WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us