On-Load Tap Changer Tester Manufacturer
Darui Electric recommends for you:
The On-Load Tap Changer Tester is based on the "Power Equipment Handover and Preventive Test Procedures" and adopts testing principles. Using microcomputer technology, it can test the performance of on-load tap changers of various power transformers without disassembling the transformer or lifting the tap changer, and display and print the waveforms and parameters of the transition process. It is a power instrument. The tester is a comprehensive measuring instrument used to measure and analyze the electrical performance indicators of on-load tap changers in power transformers and special transformers in power systems. It uses computer control and a specially designed measuring circuit to measure parameters such as transition time, transition waveform, transition resistance, and three-phase synchronization of the on-load tap changer. It can be measured directly from the tap changer leads or from the transformer's three-phase bushings and neutral point as needed.
Technical Indicators
1. Three-phase constant current output is 1A each
2. Transition time measurement: accuracy 0.1ms
3. Transition resistance measurement: accuracy 0.1Ω±5%R
4. Transition resistance measurement range: ≤25Ω
5. Transition time measurement range: <120ms
6. Three-phase synchronization: accuracy 0.1ms
7. Display three-phase waveform: accuracy 0.3ms
8. Ambient temperature: -10℃~50℃
9. Working power supply: AC220V±10% 50HZ
10. Display mode: LCD320×240 large screen liquid crystal display
11. Instrument dimensions: 360mm×260mm×150mm
12. Weight: 4.5 kg
2. Large screen dot matrix liquid crystal display, hierarchical Chinese menu.
3. Intelligent testing and result analysis, can enlarge or reduce waveform test results.
4. Three independent voltage sources are suitable for measurement without windings, and three independent constant current sources are suitable for measurement with and without windings.
5. Six independent signal processing channels, high-speed A/D conversion, 10KHz high-speed sampling, truly reflect parameter changes.
6. Built-in non-volatile memory can save three sets of waveforms and data, which can be archived, reviewed, and analyzed at any time.
7. The instrument has a built-in calendar, displays date and time, and can automatically print.
Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.